Mini Type Water Cooled Scroll Chiller, 7kW-40kW

Mini Type Water Cooled Scroll Chiller, 7kW-40kW
Mini Type Water Cooled Scroll Chiller, 7kW-40kW
Mini Type Water Cooled Scroll Chiller, 7kW-40kW
Mini Type Water Cooled Scroll Chiller, 7kW-40kW
Mini Type Water Cooled Scroll Chiller, 7kW-40kW
Mini Type Water Cooled Scroll Chiller, 7kW-40kW
Request a Quote

The water cooled chiller can be equipped with one to four scroll compressors according to the actual applications. Paired with high-efficiency shell and tube/plate condenser, evaporator and control system, this water cooled chilling unit is suitable for central air-conditioning systems in the general houses ,villas, small restaurants, shops, hotels, office and commercial buildings.

Download
Video
Technical Parameters

Model RLSW - (C) R
7
10
12
15
18
12
15
18
20
28
30
35
40
Power supply 220V/50HZ 380V/50HZ
Compressor Qty 1
Normal cooling capacity kW 8.3 10.3 12.2 15.2 / 12.2 15.2 18 19.5 27.7 29.7 34.3 40.4
Input power of cooling kW 2 2 2.8 2.8 / 2.5 2.9 3.3 3.5 5 5.4 6.6 7.2
Normal heating capacity kW 9.4 12.4 14.2 17.8 / 12.4 17.8 20.1 21.4 29.7 31.7 38.3 45.1
Input power of heating kW 2.7 2.7 3.7 3.7 / 3.4 3.9 4.5 4.7 6.8 7.3 8.4 9.8
Max. running current A 15.5 15.5 24.1 24.1 / 8 9.1 10.2 10.9 15.7 17 20 22.5
Cable diameter
(Copper wire distance≤20meters)
mm2 2*4 2*4 2*4 2*4 / 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5
Compressor type Hermetic scroll
Starting mode Direct
Refrigerant R410A
Refrigerant charge kg 1.8 1.8 4.5 4.5 / 4.5 4.5 4.5 5 6 6 6.5 6.5
Refrigerant control device Thermostatic expansion valve
Evaporator Type Plate type Tube in tube type
Water pressure drop kPa 70
Water pipe Dia. DN 25 25 50 50 / 50 50 50 50 50 50 50 50
Connection Threaded connection
Chilled water flow m3/h 1.4 1.8 2.1 2.6 / 2.1 2.6 3.1 3.4 4.8 5.1 5.9 6.9
Well water flow m3/h 0.9 1.1 1.3 1.6 / 1.3 1.6 1.9 2.0 2.9 3.1 3.5 4.2
Condenser type Type Plate type Tube in tube type
Water pressure drop kPa 70
Water pipe Dia. DN 25 25 50 50 / 50 50 50 50 50 50 50 50
Well water flow m3/h 0.9 1.1 1.3 1.6 / 1.3 1.6 1.9 2.0 2.9 3.1 3.5 4.2
Hot water flow m3/h 1.4 1.8 2.1 2.6 / 2.1 2.6 3.1 3.4 4.8 5.1 5.9 6.9
Dimensions L 1000 1000 1400 1400 / 1400 1400 1400 1400 1400 1400 1400 1400
W 610 610 655 655 / 655 655 655 655 655 655 655 655
H 730 730 1100 1100 / 1100 1100 1100 1100 1100 1100 1100 1100
Net weight kg 100 100 210 210 / 210 235 235 235 235 270 270 285
Running weight kg 120 120 248 248 / 248 280 280 280 280 325 325 340
Noise dB(A) 62 62 62 62 / 62 62 62 62 70 70 72 72
Main protection measures 1. High & low voltage protection;
2. Anti-freeze protection;
3. Temperature control;
4. Reverse phase and phase loss protection;
5. High & low pressure protection;
6. High pressure exhaust temperature protection;
7. Built-in motor overheating protection;
8. Over-current protection;
9. Safety valve;
10. Check valve;
Remarks: Cooling conditions User side inlet/outlet water temperature: 12℃/7℃; ground water inlet/outlet water temperature: 18℃/29℃;
Heating conditions User side inlet/outlet water temperature: 40℃/--℃; ground water inlet/outlet water temperature: 15℃/--℃;

Model RLSW - (C) R
7
10
12
15
18
12
15
18
20
28
30
35
40
Power supply 220V/50HZ 380V/50HZ
Compressor Qty 1
Normal cooling capacity kW 8.3 10.3 12.2 15.2 / 12.2 15.2 18 19.5 27.7 29.7 34.3 40.4
Input power of cooling kW 2 2.5 2.8 3.5 / 2.5 2.9 3.3 3.5 5 5.4 6.6 7.2
Normal heating capacity kW 9.4 12.4 14.2 17.8 / 12.4 17.8 20.1 21.4 29.7 31.7 38.3 45.1
Input power of heating kW 2.7 3.6 3.7 4.6 / 3.4 3.9 4.5 4.7 6.8 7.3 8.4 9.8
Max. running current A 15.5 15.5 24.1 24.1 / 8 9.1 10.2 10.9 15.7 17 20 22.5
Cable diameter
(Copper wire distance≤20meters)
mm2 2*4 2*4 2*4 2*4 / 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5
Compressor type Hermetic scroll
Starting mode Direct
Refrigerant R410A
Refrigerant charge kg 1.8 1.8 4.5 4.5 / 4.5 4.5 4.5 5 6 6 6.5 6.5
Refrigerant control device Thermostatic expansion valve
Evaporator Type Plate type Tube in tube type
Water pressure drop kPa 70
Water pipe Dia. DN 25 25 50 50 / 50 50 50 50 50 50 50 50
Connection Threaded connection
Chilled water flow m3/h 1.4 1.8 2.1 2.6 / 2.1 2.6 3.1 3.4 4.8 5.1 5.9 6.9
Well water flow m3/h 1.9 2.3 2.8 3.5 / 2.8 3.5 4.1 4.4 6.3 6.7 7.8 9.2
Condenser type Type Plate type Tube in tube type
Water pressure drop kPa 70
Water pipe Dia. DN 25 25 50 50 / 50 50 50 50 50 50 50 50
Well water flow m3/h 1.9 2.3 2.8 3.5 / 2.8 3.5 4.1 4.4 6.3 6.7 7.8 9.2
Hot water flow m3/h 1.4 1.8 2.1 2.6 / 2.1 2.6 3.1 3.4 4.8 5.1 5.9 6.9
Dimensions L 1000 1000 1400 1400 / 1400 1400 1400 1400 1400 1400 1400 1400
W 610 610 655 655 / 655 655 655 655 655 655 655 655
H 730 730 1100 1100 / 1100 1100 1100 1100 1100 1100 1100 1100
Net weight kg 100 100 210 210 / 210 235 235 235 235 270 270 285
Running weight kg 120 120 248 248 / 248 280 280 280 280 325 325 340
Noise dB(A) 62 62 62 62 / 62 62 62 62 70 70 72 72
Main protection measures 1. High & low voltage protection;
2. Anti-freeze protection;
3. Temperature control;
4. Reverse phase and phase loss protection;
5. High & low pressure protection;
6. High pressure exhaust temperature protection;
7. Built-in motor overheating protection;
8. Over-current protection;
9. Safety valve;
10. Check valve;
Remarks Cooling conditions User side inlet/outlet water temperature: 12℃/7℃; ground water inlet/outlet water temperature: 25℃/29℃;
Heating conditions User side inlet/outlet water temperature: 40℃/--℃; ground water inlet/outlet water temperature: 10℃/--℃;

Model RLSW - (C) R
7
10
12
15
18
12
15
18
20
28
30
35
40
Power supply 220V/50HZ 380V/50HZ
Compressor Qty 1
Normal cooling capacity kW 7.9 9.8 11.5 14.5 / 11.5 14.5 17.2 18.6 26.5 28.7 33.5 38.5
Input power of cooling kW 2.1 2.1 3 3 / 2.7 3.1 3.6 3.9 5.5 5.9 7 7.9
Max. running current A 15.5 15.5 24.1 24.1 / 8 9.1 10.2 10.9 15.7 17 20 22.5
Cable diameter
(Copper wire distance≤20meters)
mm2 2*4 2*4 2*4 2*4 / 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5 3*4 2*2.5
Compressor type Hermetic scroll
Starting mode Direct
Refrigerant R410A
Refrigerant charge kg 1.8 1.8 4.5 4.5 / 4.5 4.5 4.5 5 6 6 6.5 6.5
Refrigerant control device Thermostatic expansion valve
Evaporator Type Tube in tube type Shell and tube type
Water pressure drop kPa 70
Water pipe Dia. DN 25 25 50 50 / 50 50 50 50 50 50 50 50
Connection Threaded connection
Well water flow m3/h 1.4 1.7 2 2.5 / 2 2.5 3 3.2 4.6 4.9 5.8 6.6
Condenser type Type Tube in tube type Shell and tube type
Water pressure drop kPa 70
Water pipe Dia. DN 25 25 50 50 / 50 50 50 50 50 50 50 50
Water flow m3/h 1.7 2.1 2.5 3.1 / 2.5 3.1 3.7 4.0 5.7 6.2 7.2 8.3
Unit type Horizontal
Dimensions L 1000 1000 1400 1400 / 1400 1400 1400 1400 1400 1400 1400 1400
W 610 610 655 655 / 655 655 655 655 655 655 655 655
H 730 730 1100 1100 / 1100 1100 1100 1100 1100 1100 1100 1100
Net weight kg 100 100 210 210 / 210 235 235 235 235 270 270 285
Running weight kg 120 120 248 248 / 248 280 280 280 280 325 325 340
Noise dB(A) 62 62 62 62 / 62 62 62 62 70 70 72 72
Main protection measures 1. High & low voltage protection;
2. Anti-freeze protection;
3. Temperature control;
4. Reverse phase and phase loss protection;
5. High & low pressure protection;
6. High pressure exhaust temperature protection;
7. Built-in motor overheating protection;
8. Over-current protection;
9. Safety valve;
10. Check valve;
Remarks Cooling conditions User side inlet/outlet water temperature: 12℃/7℃; cooling water inlet/outlet water temperature: 30℃/35℃;
Features
  • Compressor characteristics and components The scroll compressor has great liquid slugging protection. After installing the oil heating device, it can effectively prevent the machine failure caused by insufficient oil-fluorine separation during operation.
  • High-efficiency shell and tube/plate evaporator and condenser allow for high heat exchange efficiency.
  • Control system With overheating protection and power supply protection, the microcomputer controller adopts wide-temperature electrical components from well-known brands. This enables it to operate reliably at an ambient temperature of-15°C to 65°C. The control system features high levels of automation. In addition, remote control is realized because of RS-232 and RS-485 standard communication interfaces.
  • Control method Microcomputer control features:
    (1) Water chilling unit controlled by the chilled water return or outlet temperature
    (2) When the load reaches the set value of the chilling unit, automatic start or stop will be performed.
    (3) LCD display screen
    (4) Inlet and return water temperature clearly displayed on the LCD screen, and the compressor's running hours can be set.
    (5) Remote control signals for start and stop can be accepted.
  • Safety protection devices Safety valve;High and low voltage switch; Anti-freeze protection; Oil heater; Temperature control ; Pressure gauge; Overload protector; Surge protector
  • Optional accessories Built-in hydraulic module or separate hydraulic module
Related products
Send Message
Inquiry
Inquiry