Inverter Testing Load Reactor

Inverter Testing Load Reactor
Inverter Testing Load Reactor
Inverter Testing Load Reactor
Request a Quote

Application
The inverter testing load reactor is capable of simulating pure inductive load to test inverters, inverters, UPS devices and motor drives.

Specification
Rated Voltage: 400V/690V/1100V
Reactance Strength: iron core-windings 3000V AC/50HZ/5mA, 10s without arcing or breakdown
Insulation Resistance: iron core-windings 1000V DC, ≥100MΩ
Reactor Noise: <65dB (tested 1 meter away from the reactor)
Standard Conformed: GB19212.1-2008, GB19212.21-2007, GB1094.6-2011

Feature
1. The inverter testing load reactor adopts high performance foil winding structure, thus receiving small DC resistance, strong short circuit endurance and high short-period overloading capacity.
2. Composite insulation materials of over level F is applied to manufacture the reactor to secure its reliability under harsh working conditions.
3. The device is designed to have low magnetic flux density, fine linearity, high overloading capacity as well as low noise, which derives from vacuum pressure varnishing techniques.
4. The iron core of the reactor is made up of high quality, low loss grain-oriented silicon steel, so that the product features tiny inductance loss, high efficiency and small temperature rise.

Related products
Send Message
Inquiry
Inquiry