20kV Dry-Type Power Transformer, Class H Insulation

20kV Dry-Type Power Transformer, Class H Insulation
Request a Quote

Applications
The 20kV dry-type power transformer is made of premium-grade insulating components, ideal for any power distribution sites as well as compact substations and mobile substations.

Standards
IEC60076
GB10094

Features
Multi-step lap core consisting of laminated iron plated stacked together and held tightly by yokes. High voltage coils come fitted with winding combs for rigid support and optimal insulation. High and low voltage windings are interconnected. The entire core-winding assembly receives vacuum pressure impregnation. The main insulation material is NOMEX insulation paper. Low core loss, minimized noise and reduced chance of partial discharge. Mechanically strong and made via innovative processes, this power transformer has high overload capacity.

20kV SGB10-30~2500/10 H-class Dry-type Transformer Parameters
Product Type Rated Voltage Vector Group No-Load loss Load loss No-load Current Impedance Voltage
H.V(kV) % L.V.(kV) (W) (W) % %
SG11-100 540 2000 2.2 4
SG11-160 20 ±2X2.5 Dyn11 680 2470 1.8
SGB11-200 22 or 0.4 or Yyn0 740 2950 1.8
SGB11-250 24 ±5 850 3420 1.6
SGB11-315 970 4090 1.6
SGB11-400 1150 4850 1.4
SGB11-500 1350 5800 1.4
SGB11-630 1530 6840 1.2 6
SGB11-800 1760 8270 1.2
SGB11-1000 2070 9790 1.0
SGB11-1250 2390 11540 1.0
SGB11-1600 2790 13870 1.0
SGB11-2000 3240 16390 1.0
SGB11-2500 3870 19380 0.8
Note: Above data are for reference only.