36kV Heat Shrink Cable Terminations and Joints

36kV Heat Shrink Cable Terminations and Joints
36kV Heat Shrink Cable Terminations and Joints
Request a Quote
  • Heat shrink cable terminations
  • Heat shrink cable joints

Description
36kV heat shrink cable terminations and joints can be used with indoor and outdoor cables with single and 3-core designs, and the max. voltage is 36kV. It can provide excellent insulation, sealing and mechanical properties to protect the cable.

36Kv heat shrink high Voltage Cable Accessories
Items Indoor/outdoor Termination Joints
Voltage rated 18/36kV 18/36kV
Partial discharge test at ambient temperature 45kV, < 10pC 45kV, < 10pC
AC withstand voltage test 117kV 5min 117kV 5min
Impulse voltage withstand ±200kV each polarity 10 times ±200kV each polarity 10 times
Partial discharge after Cyclic Aging Test 45kV, < 10pC 45kV, < 10pC
AC withstand voltage after Cyclic Aging Test 65kV,1 5min 65kV 5min
Type Size Cable range (mm2)
18/36kV XLPE cable(1-core) Indoor termination 36kVRSNY-1/1 50-120
36kVRSNY-1/2 150-240
36kVRSNY-1/3 300-630
18/36kV XLPE cable(1-core) Outdoor termination 36kVRSWY-1/1 50-120
36kVRSWY-1/2 150-240
36kVRSWY-1/3 300-630
18/36kV XLPE cable(1-core) Joint 36kVRSJY-1/1 50-120
36kVRSJY-1/2 150-240
36kVRSJY-1/3 300-630
18/36kV XLPE cable(3-core) Indoor termination 36kVRSNY-3/1 50-95
36kVRSNY-3/2 120-185
36kVRSNY-3/3 240-400
18/36kV XLPE cable(3-core) Outdoor termination 36kVRSWY-3/1 50-95
36kVRSWY-3/2 120-185
36kVRSWY-3/3 240-400
18/36kV XLPE cable(3-core) Joint 36kVRSJYF-3/1 50-95
36kVRSJYF-3/2 120-185
36kVRSJYF-3/3 240-400

Standard: IEC 60502

Related products