Heat Shrink Anti-Tracking Tube
Request a Quote
Model: CYG-RSWT
Applications
Heat shrink anti-tracking tubes are typically used for indoor and outdoor 36kV voltage grade power cable insulation tubing because of its excellent weather resistance, aging resistance and flame resistance.
Size | as supplied(mm) | After recovery (mm) | Cable range(m2) | |
Diameter | diameter | wall | ||
RSWT—30/11 | ≥28 | ≤11 | 2.7±0.25 | 25~50 |
RSWT—35/13 | ≥33 | ≤14 | 2.8±0.25 | 70~120 |
RSWT—40/15 | ≥38 | ≤15 | 3.0±0.4 | 150~240 |
RSWT—45/17 | ≥43 | ≤18 | 3.0±0.4 | 300~400 |
RSWT—50/22 | ≥48 | ≤23 | 3.3±0.4 | Special design |
RSWT—60/22 | ≥58 | ≤23 | 3.3±0.4 | |
RSWT—80/27 | ≥74 | ≤30 | 3.7±0.4 | |
RSWT—100/37 | ≥94 | ≤40 | 3.9±0.4 | |
RSWT—120/37 | ≥118 | ≤45 | 3.6±0.4 | |
RSWT—140/49 | ≥138 | ≤55 | 5.0±0.4 | |
RSWT—160/66 | ≥158 | ≤70 | 6.0±0.4 |
Items | Unit | Specifications | Test methods |
Tensile strength | MPa | ≥8.0 | ASTM D2671 |
Elongation at break | % | ≥300 | ASTM D2671 |
heat aging | K1>0.8 K2>0.7 | 120℃ 168h | |
Volume resistance | Ω· cm | ≥1014 | ASTM D2671 |
Dielectric strength | kV/mm | ≥20 | ASTM D2671 |
Shrink temperature | ℃ | 120~140 | |
Anti tracking Voltage grade | A level | ≥3.5 | ASTM D2303 |
Oxygen index | OI | ≥28 | ASTM D2863 |
Water absorption | ≤0.5% | ASTM D570 |