RHH RHW-2 USE-2 Cable

RHH RHW-2 USE-2 Cable
Request a Quote

RHH/RHW-2/USE-2 cable has a compact stranded AA-8000 series aluminum alloy conductor with cross-linked polyethylene (XLPE) insulation. It is sunlight, abrasion, moisture and heat resistant.

RHH/RHW-2/USE-2 cable is to be used at conductor temperatures up to 90℃, RHH cable for uses in dry locations and RHW-2/USE-2 cable for uses in dry, damp or wet locations. The voltage rating is 600V.

Applications:

RHH/RHW-2/USE-2 cable is suitable for direct burial or underground duct as specified in the NEC.

Standards:

RHH/RHW-2/USE-2 cable meets UL 44 and UL 854. It has passed the following tests: current overload test, FT2 horizontal flame test, 720h sunlight resistance test, aging test on insulation materials, dielectric voltage withstand test, etc.

Specifications:

Conductor Size (AWG or kcmil)

Nominal Cond. Diameter Normal

Insulation Thickness

Nominal Thickness

Approx. Weight

Allowable Ampacities
Inch mm mils mm mils mm Kg/Km LBS/1000FT 60℃ 75℃ 90℃
8 0.134 3.4 60 1.52 254 6.4 27 18 35 40 45
6 0.169 4.29 60 1.52 289 7.3 31 21 40 50 55
4 0.213 5.41 60 1.52 333 8.5 37 25 55 65 75
2 0.268 6.81 60 1.52 388 9.9 45 30 75 90 100
1 0.299 7.59 80 2.03 459 11.7 69 46 85 100 115
1/0 0.336 8.53 80 2.03 496 12.6 75 50 100 120 135
2/0 0.376 9.55 80 2.03 536 13.6 81 54 115 135 150
3/0 0.423 10.74 80 2.03 583 14.8 89 60 130 155 175
4/0 0.475 12.07 80 2.03 635 16.1 99 67 150 180 205
250 0.520 13.21 95 2.41 710 18.0 128 86 170 205 230
300 0.570 14.48 95 2.41 760 19.3 139 93 195 230 260
350 0.616 15.65 95 2.41 806 20.5 146 98 210 250 280
400 0.659 16.74 95 2.41 849 21.6 155 104 225 270 305
500 0.736 18.69 95 2.41 925 23.5 169 114 260 310 350
600 0.813 20.65 110 2.79 1033 26.2 216 145 285 340 385
700 0.877 22.28 110 2.79 1097 27.9 230 155 315 375 425
750 0.908 23.06 110 2.79 1128 28.6 237 159 320 385 435
900 0.999 25.37 110 2.79 1219 31.0 254 171 355 425 480
1000 1.060 26.92 110 2.79 1280 32.5 266 179 375 445 500